Digital controller module SD7
                                                                                            Digital controller modul

            CONTROLLER MODULE SD7
            Command value scaling                                Controller mode «Pressure/flow valve control (1-sol)»
            The command value can be applied via the fieldbus or as a voltage,   Control of  a 1-solenoid pressure relief,  pressure reducing,  throttle
                                                     P
            current, digital, frequency or PWM signal. The input used can be   or flow control valve in closed control circuit (with feedback value
                       P
            selected for each command value. The scaling is carried out via   signal). Only one solenoid can be controlled with it (corresponds to
            the  «Interface» and «Reference» parameters.  Furthermore,  each   the solenoid driver 1).
                                                                  SD7
                                                           P
                                                                          w
                                                            Xi
            command value can be monitored for cable break (except HART,   P
                                         x
                              P
                                                w
                                      SD7
            voltage and digital signal). For every command value, a dead band                Q                      P
                               Xi
         x  can  also  be  set.  Optionally  one can  operate  with  two command   Q
                             t
                              Xi
            values. The characteristic of these command values can be adjusted.  P Xi  SD7  w  Q Xi      SD7     w
 t                                                     x                                                   Q
 Xi         Profiles/Fixed command values (Enhanced controller only)  Q Xi          SD7       w                              P          SD7          w
                             SD7
            There are 7 fixed command values available, which can be selected                                                  Xi
                                          t
                                           Xi
            via 3 digital inputs. Optionally, travel profiles can also be used. The               x       Q Xi        SD7      w                                                  Q
            SD7 controller module is able to store and to travel whole travel
                             w
 SD7        profiles, which have been previously generated by the user in the
                                          SD7
            profile generator. A travel profile consists of the following data:  t
             •  Target position (target or end position of the sequence)         Xi                                                                                              Q                  SD7          w
 w           •  Speed (of the travel)      w          P                                                                                                                            Xi
             •  Acceleration (to reach the speed)                Controller mode «Pressure control (2-sol)»
                              V
                               Xi
             •  Deceleration (starting from the speed)     P     Control of two 1 solenoid throttle valves in closed control circuit (with
             •  Stop time (after reaching the end position of the sequence)  Xi  feedback value signal) as pressure control. The one throttle valve
                                                                               SD7
                                                                                                     P
                                    w
                        P
                                                                   P
             •  Setting of a digital output when reaching the end position    serves as a loading valve and the other as an unloading valve. The
 V            of the sequence              V Xi                  loading valve corresponds to the solenoid driver 1, the unloading
                                                          SD7
 Xi          •  Adjust whether the command value or the feedback value for the   valve corresponds to the solenoid driver 2.
                                                                        P
                              P
                                   SD7
              end of the sequence is to be queried  w                    Xi
                               Xi
   w                                                       w                    P w                  P             P
            Command value generator                                                                   Xi
            In the open-loop controller modes, there are two linear ramps for up   SD7
                                                SD7
                             SD7
            and down per solenoid output are available, which can be adjusted
                                                     P
 SD7        separately. In the closed-loop controller modes, there is a positive and   w            SD7           P
            a negative travel speed available.                                                                     Xi  P
                              w                                                P Xi                  w
                                    w
            HOLD command value (option fieldbus only)             P             V                                 SD7
                             Xi
            If via fieldbus the device is put into the «HOLD» state, the respective   Xi                                     P
                                                         t
                                                          Xi
                       P
            command value is activated.                                        SD7                                             Xi
                                   SD7                                                                             w
            Feedback value scaling         Xi     w     SD7                               w                                                                                                   P
            The feedback value can be applied via HART or as voltage, current,   t  Xi  w
   w        frequency or PWM signal. For the feedback value, the input used                                                  SD7
                                                SD7
                                                         w
 Xi         can be selected. The scaling is carried out via the «Interface» and
                           t
            «Reference»  parameters.  In  addition,  the  feedback  value  can  be   SD7  SD7
                            Xi
            monitored for cable break (except HART and voltage signal).  Controller mode «Axis position controlled»
 SD7                                                             Control of  a spool valve in open control circuit  (without  feedback
                                                                       w
            Manual operation (Enhanced controller only)          value signal). The number of solenoids controlled depends on the   w                                                         P Xi
                           SD7
            The commands Enable, Forward, Reverse and Fast speed are   selected mode of operation.
            available. This makes it possible to move the cylinders through a
            superimposed control without specifying a command value.  Controller mode «Axis position controlled (2-sol)»
                            w                                    Control of a 2-solenoid spool valve in closed control circuit (with   P
            Window                                               feedback value signal). Two solenoids can be controlled with it.                                                            SD7
            A target, tracking error and solenoid stop window is available. The
            threshold and delay time can be set for each window.
                                                                                                                                                                                              w
            Controller
            The SD7 controller module has a controller circuit. This is built up as       w
            PID controller. The following controller modes can be selected:     Xi                                        t
                                                                                                                           Xi
            Controller mode «Pressure/flow valve control»
            Control of a pressure relief, pressure reducing, throttle or flow control   SD7
            valve  in  open  control  circuit  (without  feedback  value  signal).  The
            number of solenoids controlled depends on the selected operating                                              SD7
            mode of operation.
                                                                                                                           w
            Wandfluh AG         Tel.  +41 33 672 72 72   sales@wandfluh.com     Illustrations not obligatory   Data sheet no.
            Postfach            Fax  +41 33 672 72 12   www.wandfluh.com        Data subject to change   1.13-106E 5/11
            CH-3714 Frutigen                                                                             Edition 23 02
                                                                                                            Page 745
   740   741   742   743   744   745   746   747   748   749   750