Page 7 - Oil+Gas_EN
P. 7

EX-PROTECTION STANDARDS  TYPE OF PROTECTION  SYMBOL       ZONE            DIAGRAM              STANDARD
                      TYPES OF PROTECTION FOR ELECTRICAL EQUIPMENT IN GAS EXPLOSION HAZARD AREAS


                                                                                                IEC 60079-7
 DESIGNATION OF ELECTRICAL EQUIPMENT  increased safety  e    1                                EN 60079-7 (ATEX)

 ATEX     I  M1  Ex  ia  I  Ma
                flameproof enclosure         d               1                                  IEC 60079-1
 IEC  Ex  ia  I  Ma                                                                           EN 60079-1 (ATEX)
 ATEX     II  1G  Ex  ia  IIC  T5/T6  Ga
                intrinsic safety             ia              0                                  IEC 60079-11
 IEC  Ex  ia  IIC  T5/T6  Ga                                                                  EN 60079-11 (ATEX)
 ATEX     I  M2  Ex  d, db  I  Mb
                encapsulation                m               1                                  IEC 60079-18
 IEC  Ex  d, db  I  Mb                                                                        EN 60079-18 (ATEX)
 ATEX     II  2G  Ex  d, db  IIC  T4/T6  Gb
 IEC  Ex  d, db  IIC  T4/T6  Gb
                      TYPES OF PROTECTION FOR ELECTRICAL EQUIPMENT IN AREAS WITH COMBUSTIBLE DUST
 ATEX     II  2D  Ex  tb  IIIC  T80 °C/T130 °C  Db
                TYPE OF PROTECTION         SYMBOL          ZONE            DIAGRAM              STANDARD
 IEC  Ex  tb  IIIC  T80 °C/T130 °C  Db
 NEC 505  Class I, Zone 1  AE x  d  IIC  T4  Gb  protection by enclosures  tb  21               IEC 60079-31
                                                                                              EN 60079-31 (ATEX)
 NEC 500  Class I, Division 1  ABCD  T4
                old identification: tD A21 = under procedure A for zone 21 (EN 61241-1)
 ZONES
                      GROUPS
 dangerous explosive atmosphere  continuously, frequently or long-term  occasionally  not likely to occur and for short periods only
 ATEX / IEC / NEC 505  Zone 0  Zone 1  Zone 2  ATEX / IEC / NEC 505                  NEC 500
 Gas
 NEC 500 (Class I)  Division 1  Division 2  Group I  mines susceptible to firedamp      —
 ATEX / IEC / NEC 505  Zone 20  Zone 21  Zone 22  Methan
 Dust
 NEC 500 (Class II, III)  Division 1  Division 2  Group II  gas explosion hazard areas  Class I
 Zone 0 (20) includes zones 1 and 2 (21 and 22)  subdivisions  typical gas              subdivisions
                IIA                    Propane                  Propane                 Class I Group D
                IIB                    Ethylene                 Ethylene                Class I Group C
                IIC                    Hydrogen                 Hydrogen                Class I Group B
                                       Acetylene                Acetylene               Class I Group A
                Groupe III             dust explosion hazard areas                      Class II/III
                subdivisions           type of dust                                     subdivisions
                IIIA                   combustible flyings      fibres and fluff        Class III
                IIIB                   non-conductive dust      non-conductive dust     Class II Group G
                IIIC                   conductive dust          carbonaceous dust       Class II Group F
                                                                combustible metal dust  Class II Group E
 EQUIPMENT CATEGORY AND EQUIPMENT PROTECTION LEVEL (EPL)
                Subdivision IIC (IIIC) includes subdivisions IIA and IIB (IIIA and IIIB)
 ATEX  IEC
 Equipment group  Equipment category  EPL  sufficient security
                      TEMPERATURE CLASSIFICATION
 mines susceptible to firedamp
 I  M1  Ma  during rare malfunctions  Maximum   Temperature classes for gases  Maximum surface temperature  Temperature classes for gases
                surface temperature
 I  M2  Mb  until de-energizing of the equipment  ATEX / IEC / NEC 500 / 505           ATEX / IEC / NEC 500 / 505
 gas explosion hazard areas  450 °C             T1                      200 °C                    T3
 II  1G  Ga  Zone 0  during rare malfunctions  300 °C  T2               135 °C                    T4
 II  2G  Gb  Zone 1  during expected malfunctions                       100 °C                    T5
                for dusts: indication of the maximum surface temperature in °C
 II  3G  Gc  Zone 2  in normal operation                                85 °C                     T6
 dust explosion hazard areas
 II  1D  Da  Zone 20  during rare malfunctions
                      TYPE OF PROTECTION
 II  2D  Db  Zone 21  during expected malfunctions
 II  3D  Dc  Zone 22  in normal operation  IP Type of protection according to IEC/EN 60529






               WANDFLUH OIL + GAS    |        PROPERTIES      |        EX-PROTECTION STANDARDS   |        PAGE 5
   2   3   4   5   6   7   8   9   10   11   12